RS-485 is the wire, Modbus RTU is the language that runs on it, and 4-20 mA is a separate analog signal that carries one value per pair of wires. They are not three rival options. On a real rectifier they do three different jobs, and a line that needs recipes and readback plus a hard interlock usually wants more than one of them. The number most buyers never ask for is the poll time: at 9,600 baud, reading ten registers from 32 rectifiers takes about 1.1 seconds. If your control loop needs 100 ms, that digital link is already too slow.
Standards and bodies that show up in a serious spec: IEC 61378-1 (industrial converter transformers), IEEE C57.18.10 (semiconductor rectifier transformers), Modbus Organization (RTU specification), IEC 61158 / IEC 61784 (fieldbus profiles), IEC 61000-6-2 (immunity for industrial locations), and NEMA / UL for the panel itself. None of them tells you which interface to buy. That is what this page is for.
The short answer: three layers, not three rival interfaces
If you remember one thing from this page, make it this. The search phrase itself mixes up categories, and so do a lot of supplier pages.
RS-485 is a physical layer
RS-485 defines electrical signals on two wires, usually labelled A and B. A difference of about 200 mV at the receiver is enough to decide a logic state. The driver must put out at least 1.5 V into a 54 ohm load. The receiver tolerates a common-mode voltage from minus 7 V to plus 12 V. That is why it survives in plants where a single-ended signal would not.
RS-485 does not define a single bit of data meaning. It says nothing about addresses, function codes, or scaling. On its own it is just a very good way to move a differential voltage around a noisy room.
Modbus RTU is a protocol that usually rides on RS-485
Modbus RTU defines the frame: slave address, function code, data, and a 16-bit CRC. One master polls, one or many slaves answer. A slave never speaks unless asked. That last rule matters more than most buyers realize, and we come back to it in the section on alarms.
You can run Modbus RTU over RS-485, over RS-232, or over TCP. When a supplier says “Modbus”, ask which physical layer they mean. “Modbus TCP” and “Modbus RTU over RS-485” are different wiring, different cabling, and different troubleshooting.
4-20 mA is an analog current loop, not a bus
A 4-20 mA loop carries one value by varying current. Four milliamps means the low end of the scale, twenty means the top. Because the information is in the current, not the voltage, wire resistance does not change the reading as long as the transmitter still has enough voltage to push the current. That is the whole reason the industry uses it over long cable runs.
It is also why it cannot carry much. One loop, one number. No recipe name, no fault log, no timestamp, no internal temperature, no “thyristor 3 is running hot”.
PLC integration is the system job, not the interface
The PLC does not care which physical layer you picked. It wants a setpoint to write, a readback to poll, a few discrete inputs for permissives, and a clean way to raise an alarm. The interface is how those things travel. The integration is what they mean.
| Layer | What it is | What it gives you on a rectifier | What it cannot do |
|---|---|---|---|
| RS-485 | Differential physical layer | Two-wire multi-drop cabling, long reach, noise immunity | No data format, no addressing |
| Modbus RTU | Application protocol on RS-485 or TCP | Multiple registers, status, alarms, recipes, readback | Slave cannot initiate; poll delay |
| 4-20 mA | Analog current loop | One solid setpoint or readback, live-zero fault detection | One value only, no diagnostics |
| PLC / SCADA | System layer | Sequencing, recipes, data logging, interlocks | Nothing without the lower layers |
What each layer actually carries on a rectifier
Walk into any plating or anodizing line and you will find five different kinds of information moving between the PLC and the rectifier. They do not all belong on the same wire.
Setpoint: who tells the rectifier what to do
For a simple remote setpoint, 4-20 mA is hard to beat. The PLC writes an analog output, the rectifier reads it as the current or voltage command, and the operator sees the same number on both screens. No protocol stack, no address table, no register map to argue about.
For anything with more than one number, use Modbus. A ramp profile needs a target current, a target voltage, a ramp time, a dwell time, and a mode bit. That is five values, which is five analog outputs if you insist on going analog. One Modbus write of five holding registers does the same job.
Readback: what comes back
Analog readback gives you the actual DC current and voltage as two 4-20 mA outputs from the rectifier. It is deterministic and it is isolated. Digital readback gives you the same two values plus the chopper temperature, the cooling fan status, the mains voltage, the accumulated ampere-hours, and the last eight faults. If you are doing quality traceability, the digital readback is the one you want in the database.
Recipes and ramps
A job shop that runs ten different parts a shift needs stored recipes. That is a digital feature. Write the recipe table into the rectifier over Modbus, then let the PLC send a single “load recipe number” command. Trying to encode recipes in analog signals is possible and miserable.
Interlocks and alarms
Here is the trap. In Modbus RTU, the slave cannot call the master. If the rectifier trips on overtemperature, it cannot tell the PLC until the PLC asks. So the question “did you see the fault?” has an answer that depends on your poll rate.
Use hardwired contacts for anything safety-related. A dry contact from the rectifier’s fault relay into a PLC digital input announces a trip immediately and cannot be lost to a busy bus. Use Modbus for the detail: which fault, when it happened, what the readings were. Use the analog live-zero feature for the third case, which we cover next.
Diagnostics
Fault history, cooling status, fan hours, thyristor firing angle, communication error counters. None of this fits in a current loop. If your maintenance team is expected to diagnose a rectifier remotely, budget for the digital link.
| Information | Best carrier | Why |
|---|---|---|
| Single current or voltage setpoint | 4-20 mA | Simple, isolated, no software |
| Actual DC current and voltage | Both | Analog for the loop, digital for the log |
| Recipe number and ramp profile | Modbus RTU | Multiple values in one write |
| Overtemperature / fault trip | Hardwired relay contact | Instant, independent of polling |
| Loss of signal wire | 4-20 mA live zero | Current below 4 mA means broken wire |
| Fault history and diagnostics | Modbus RTU | Timestamps and multiple fields |
Wiring the analog loop without fooling yourself
Most 4-20 mA problems are not protocol problems. They are voltage-budget problems that nobody drew on the schematic.
The 24 V loop budget
A two-wire loop has to power the transmitter and push current through the wire and the PLC input resistor. Add it up before you pull cable.
Take a 24 V supply, a PLC analog input with a 250 ohm resistor, and a transmitter that needs at least 12 V to stay alive. At 20 mA, the drop across the 250 ohm input is 5 V. That leaves 19 V for the transmitter and the wire. The maximum total loop resistance is the supply minus the transmitter floor, divided by 20 mA: 12 V over 0.020 A gives 600 ohm. Subtract the 250 ohm input and you have 350 ohm left for the entire cable run, out and back.
Copper loop resistance is roughly 0.1 ohm per metre for a typical 1.5 mm2 pair. A 500 m round trip is 50 ohm, well inside the budget. A 3 km run is 300 ohm, right at the edge, and any extra contact resistance pushes the transmitter into dropout. When that happens the current collapses, the PLC sees a low reading, and everyone blames the rectifier.
Live zero: the trick analog still wins with
A 0-20 mA signal cannot tell you whether a reading of zero is real or whether the wire fell off. A 4-20 mA signal can. Anything below 4 mA is impossible in normal operation, so a reading of 3.6 mA is a broken wire or a dead transmitter. That is called live zero, and it is the reason the industry never moved entirely to digital.
Wire the PLC scaling so the low end alarm fires below, say, 3.6 mA rather than exactly 4.0 mA. Give it a small deadband or you will chase nuisance alarms every time the transmitter warms up.
Resolution: 12-bit versus 16-bit over 16 mA
The useful span is 16 mA, not 20. On a 12-bit converter that is 16 divided by 4,095, or 3.907 microamps per count, which is 0.0244 percent of span. On a 16-bit converter it is 0.2441 microamps per count, or 0.00153 percent of span.
For a plating rectifier where ±1 percent current regulation is the spec, 12-bit is already ten times finer than you need. Do not pay for 16-bit analog inputs unless your process actually resolves it. Spend the money on an isolated input instead.
Sourcing, sinking and loop power
Before you order, decide who powers the loop. The PLC can source 24 V to a passive rectifier interface, or the rectifier can drive its own output and the PLC input reads it. Those are different wiring diagrams. Get the drawing agreed in writing, including whether the PLC input is sourcing or sinking, because a mismatch here is the classic commissioning day-one failure.
Building a Modbus register map you can hand to a PLC programmer
A supplier who says “we support Modbus” has told you almost nothing. Ask for the register map as a spreadsheet before the order, and check that it uses standard function codes.
Function codes that matter
- 03 Read Holding Registers. The workhorse for reading measured values and settings.
- 06 Write Single Register. Fine for one setpoint.
- 16 Write Multiple Registers. Use this for recipes and ramps. It is one frame instead of five.
- 04 Read Input Registers. Some vendors put measurements here instead of in holding registers. Ask which.
Anything that needs a vendor DLL or a custom driver is not Modbus in any useful sense. If the map requires a proprietary tool, treat it as a custom protocol.
An example map
This is a representative map, not any specific product. Use it as a template for the document you demand from your supplier.
| Address | Function | Content | Scaling |
|---|---|---|---|
| 40001 | 03 / 06 | Current setpoint | 1 count = 0.1 A, unsigned 16 |
| 40002 | 03 / 06 | Voltage setpoint | 1 count = 0.1 V, unsigned 16 |
| 40003 | 03 | Actual DC current | 1 count = 0.1 A, unsigned 16 |
| 40004 | 03 | Actual DC voltage | 1 count = 0.1 V, unsigned 16 |
| 40005 | 03 | Control mode, 0 = CC, 1 = CV | Enumerated |
| 40006 | 03 | Fault word 1 | Bitfield |
| 40007 | 03 | Cooling temperature | 1 count = 0.1 C, signed 16 |
| 40008 | 03 | Ampere-hours, low word | Unsigned 16 |
| 40009 | 03 | Ampere-hours, high word | Unsigned 16 |
| 40010 | 03 / 06 | Active recipe number | 1 to 32 |
Scaling, byte order and the 16-bit trap
Three arguments cause more integration delays than anything else. First, scaling: 1,000 A at 0.1 A per count is 10,000, which fits in a 16-bit register. At 0.01 A per count it is 100,000, which does not. Above 65,535 you need two registers, and someone has to decide which one is the high word.
Second, byte order. Modbus registers are 16 bits, but a 32-bit value needs two of them. Big-endian and little-endian both exist in the wild. Write the expected value into the map as an example. “Register 40008 = 0x2DC8 when ampere-hours = 117.20” removes the ambiguity faster than any specification sentence.
Third, signed versus unsigned. A negative temperature reading in an unsigned register appears as 65,000-something. State the type in the map.
Addresses, drivers and the 32-node reality
Modbus allows slave addresses 1 to 247. RS-485 drivers are specified in unit loads, and a standard segment supports 32 unit loads. Modern 1/8-load transceivers stretch that to 256 on paper, but cable length and noise usually set a lower practical limit.
If a vendor claims 128 rectifiers on one 38,400 baud bus, ask for the poll cycle at that count. The claim may be electrically true and operationally useless.
How fast is it really? The polling math
This is the section most buyers never ask for, and it decides whether Modbus is suitable at all.
Bits, characters and frames
Modbus RTU in the usual 8N1 format uses 10 bits per character: 1 start, 8 data, no parity, 1 stop. At 9,600 baud one character takes 1.042 ms. A request to read ten holding registers is 8 bytes: address, function code, two bytes of start address, two bytes of quantity, and two bytes of CRC. The response is 25 bytes: address, function code, byte count, twenty bytes of data, and CRC.
Adding a conservative inter-frame gap, one exchange is about 38 ms at 9,600 baud. At 19,200 baud it is about 19 ms. At 115,200 baud it is about 3 ms.
Worked: 32 rectifiers at 9,600 baud
Multiply the 38 ms exchange by 32 slaves and you get roughly 1.2 seconds for a full sweep of ten registers per rectifier. Our round figure of 1.1 seconds uses a tighter gap; either way, the order of magnitude is what matters.
At 19,200 baud the same sweep is about 0.55 seconds. At 115,200 baud it is about 0.09 seconds, but high baud rates shorten the usable cable dramatically. Typical figures are 1,200 m at 9.6 kbps, around 1,000 m at 19.2 kbps, roughly 550 m at 38.4 kbps, and about 100 m at 115.2 kbps. You trade reach for speed.
When Modbus is too slow
If you want the PLC to close a current loop over the serial link, with a 100 ms update, the math says no. A single-slave 115,200 baud link might make it. A 32-node 9,600 baud bus cannot.
The correct architecture is to close the fast loop locally in the rectifier and use Modbus for supervision. Let the rectifier regulate current against its own analog setpoint, and let the PLC adjust that setpoint a few times a second. If the PLC must close the loop, use the analog output and analog input, not the bus.
Poll fast-changing values at 100 to 500 ms and slow parameters at 1 to 5 seconds. Do not poll everything every cycle. A well-designed map splits fast and slow registers so the master is not dragging 30 temperature values through the bus ten times a second.
The rectifier room is a hostile place for small signals
A rectifier is a noise generator. Every thyristor commutation pulls a sharp current step out of the mains, and the DC side carries ripple at a multiple of the line frequency. A six-pulse bridge produces ideal characteristic distortion of 31.084 percent on the AC side and ripple at 360 Hz on a 60 Hz supply. A twelve-pulse bridge drops those to 15.219 percent and 720 Hz. That energy is sitting in the same cabinet room as your 4-20 mA wiring.
What the rectifier does to the ground
Large DC currents and imperfect return paths create potential differences between grounding points. A signal cable running between two points that are one volt apart has one volt of common-mode voltage on it. With a receiver offering 80 dB common-mode rejection, a 1 V difference produces roughly 0.1 mV of error. Across a 250 ohm input that is about 0.0025 percent of a 4 V span, which sounds harmless until the ground difference is ten times larger or the CMRR is worse at the frequency of the noise.
The more dangerous case is a fault that lifts the ground by hundreds of volts. An unbuffered analog input does not survive that.
Why 4-20 mA is not immune
The current loop ignores series resistance. It does not ignore common-mode voltage. A 4-20 mA receiver still has two wires and a finite common-mode range. If the transmitter and the PLC sit on different grounds, or if a long cable picks up switching noise, the receiver can be pushed outside its linear range. The fix is not “use current instead of voltage”. The fix is isolation.
Physical rules that actually work
- Route signal cable separately from power cable. Aim for at least 200 mm of separation, and cross at right angles when you must cross.
- Use shielded twisted pair. Ground the shield at one end only, normally the control-room end, so no shield current circulates.
- For RS-485, put a 120 ohm terminating resistor at each physical end of the bus and nowhere else. A resistor on a stubbing node adds load and makes the problem worse.
- Daisy-chain the bus. Keep branch stubs under 0.3 m. A star topology is the most common cause of intermittent serial faults.
- Use isolated transceivers at segment boundaries. Isolation ratings of several kilovolts are common and worth the money here.
- Use isolated analog input modules, ideally per-channel isolation, so one bad loop cannot drag down its neighbours.
Isolation is not optional
In a rectifier room, an isolator is not a nice-to-have accessory. It breaks the ground loop, blocks common-mode injection, and protects the PLC input from a ground-potential event. Specify the isolation voltage, the common-mode range, and the fact that the isolator must be on both the analog and the digital link if both cross between different grounding zones.
Choosing the interface set for your line
A job shop running mixed work
You need recipes, a local HMI, and simple readback. Specify Modbus RTU plus a local operator panel, and keep one 4-20 mA output for the plant recorder if an older system expects it. Poll a handful of registers, not the whole map.
A dedicated high-current line
Current regulation is the process. Run the setpoint and readback as isolated 4-20 mA so the control loop never waits on a serial poll, and use Modbus for recipes, logging and diagnostics. Add hardwired fault contacts to the line PLC. This is the configuration that keeps production running when the serial link is being debugged.
A retrofit on a legacy PLC
Look at what the PLC already has. An old panel with spare analog inputs but no serial port is a 4-20 mA job. Add a serial module later if diagnostics become worth it. Do not force a protocol conversion into a panel that has no room for it.
A new line on an industrial network
If the plant standard is EtherNet/IP, Profinet or Modbus TCP, ask the rectifier supplier for a gateway or a native interface, and keep Modbus RTU at the device level as the common denominator. Confirm that the gateway exposes the same register map rather than a simplified subset.
Commissioning: how to prove it works before you accept it
Ask for these tests on site, with your PLC and your cable, not on the supplier’s bench.
Loop check at 4, 12 and 20 mA
Inject or command each point and confirm that the PLC reads the correct engineering value at all three. Twelve milliamps should give exactly mid-scale. Check the live-zero alarm at 3.6 mA. This catches scaling errors before they become product-quality problems.
Register readback and error counters
Read every register in the map and compare against the local HMI. Then leave the link running for an hour and check the CRC error counter. Zero errors under load is the target. A handful of errors per hour means a wiring or termination problem, not a software problem.
Scope the A/B pair
Put a differential probe on the bus at the far end, not at the master. The waveform should show clean transitions with flat plateaus. Rounded or ringing edges mean termination or stub length trouble. This single check resolves most “intermittent Modbus” cases.
Force a fault
Trip the rectifier on purpose, with the load safely isolated, and confirm that the hardwired contact arrives at the PLC immediately and that the fault code arrives over Modbus afterwards. If the fault code never arrives because polling stopped, you have found the weakness in the design before the customer finds it.
What to write in the RFQ
Copy this block into your enquiry. Replace the brackets. It removes most of the back-and-forth.
- Process and duty: [plating / anodizing / electrolysis], [rectifier count], [DC current and voltage].
- Analog interfaces: [number] x 4-20 mA setpoint input, [number] x 4-20 mA readback output, isolated, [sourcing / sinking] as agreed.
- Digital interface: Modbus RTU over RS-485, baud rate [9,600 / 19,200], slave addresses [range], parity [8N1 / 8E1].
- Register map: supplier to provide a spreadsheet with address, function code, scaling, data type and byte order before order release.
- Hardwired I/O: [number] fault relay contacts, [number] permissive inputs, voltage-free contacts.
- Local HMI: [yes / no], with [recipe count] stored programs.
- Isolation: analog and serial isolation voltage [value], common-mode range [value].
- Cable interface: shielded twisted pair, 120 ohm termination at bus ends, daisy-chain topology, max stub 0.3 m.
- Update rate: fast registers polled at [100 to 500] ms, slow registers at [1 to 5] s.
- Commissioning: site loop check at 4 / 12 / 20 mA, register map verification, one-hour CRC error log, forced fault test.
- Documentation: as-built wiring drawings, register map, PLC tag list, and a sample Modbus Poll capture.
FAQ
Is RS-485 the same thing as Modbus? No. RS-485 is an electrical physical layer that moves differential signals over two wires. Modbus RTU is an application protocol that defines frames, addresses, function codes and CRC checks. Modbus usually runs on RS-485, but it can also run over TCP. A supplier who says “RS-485 communication” without naming a protocol has not told you how to talk to the device.
Can I use 4-20 mA instead of Modbus and skip the protocol work? For a single setpoint and a single readback, yes. For recipes, fault history, temperature monitoring and ampere-hour totals, no. One current loop carries one number. Most rectifier installations end up with both: analog for the fast control path, digital for data.
How many rectifiers can sit on one RS-485 bus? A standard segment supports 32 unit loads. With 1/8-load transceivers the electrical limit rises to 256, but cable length, baud rate and noise usually reduce the practical number. At 9,600 baud a typical maximum cable length is about 1,200 m, falling to roughly 100 m at 115,200 baud.
Why do I need a 120 ohm resistor, and where does it go? It matches the cable impedance and stops signal reflections on long runs. Put one at each physical end of the bus and nowhere else. Adding resistors at intermediate nodes loads the drivers and can break communication that was previously fine.
How long does a Modbus poll take? At 9,600 baud in 8N1, one character takes 1.042 ms and a ten-register read takes about 38 ms including a conservative gap. Thirty-two rectifiers on that bus need roughly 1.1 to 1.2 seconds for one full sweep. Doubling the baud rate roughly halves the time but shortens the allowable cable.
Can a rectifier send an alarm without being polled? Not over Modbus RTU. Slaves only answer requests. Use a hardwired fault relay into a PLC digital input for anything safety-related, and use the digital link for the fault detail afterwards.
What does live zero mean in a 4-20 mA loop? It means the valid signal starts at 4 mA rather than zero, so any reading below 4 mA indicates a broken wire or a failed transmitter. Set the fault threshold slightly below 4 mA, around 3.6 mA, to avoid nuisance alarms.
Why does the analog reading drift only when the rectifier is loaded? Most likely common-mode voltage or a ground loop, not the current loop itself. Check the shield is grounded at one end, confirm the signal cable is separated from power cable, and add an isolated analog input or isolator between the rectifier and the PLC.
Should I specify a 16-bit analog input for better accuracy? Only if the process needs it. Across the 16 mA span, a 12-bit input resolves 3.907 microamps per count, about 0.0244 percent of span, which is already better than a typical ±1 percent rectifier. Put the money into isolation first.
What should I ask a supplier before I place the order? Ask for the register map as a spreadsheet, the exact baud and parity, the isolation voltage on both analog and serial links, the number of hardwired fault contacts, and a sample communication capture from a real unit. If they cannot produce these, the integration will be done on your time.